Welcome to chapter three, circuit protection and capacitors. In chapter one we saw that heating rises with the square of the current, so a fault that lets the current run away can melt a cable and start a fire within seconds. In the first part of this chapter we meet the devices that stop that happening: fuses of several kinds, current limiters, and the circuit breakers you will find in rows on every flight deck, including the important difference between trip-free and non-trip-free breakers. In the second part we turn to the capacitor, a component that stores charge, blocks direct current and seems to pass alternating current, and we learn how fast it charges using the time constant.
Chapter 3
Protecting circuits, and storing charge Part 1: circuit protection , so a fault cannot overheat cables or equipment. Part 2: the capacitor .
Faults and timing Short circuits and overloads. Why a fuse acts before full fault current and a breaker after it.
Fuses Cartridge, HRC and dummy fuses, current limiters. Rating, replacement and spares.
Circuit breakers Thermal trips, the white band, trip-free versus non-trip-free, reverse current breakers.
Capacitors Capacitance, working voltage, time constant, DC and AC behaviour, series and parallel.
Chapter 3 · Circuit Protection and Capacitors
2
e-books by eatpl.in · © 2026 · Do not copy or distribute
Here is the plan for this chapter. The first part is about circuit protection. We look at the faults that can make current run away, and why a fuse acts before the fault current reaches its maximum while a circuit breaker acts after. Then we look at fuses: cartridge fuses, high rupture capacity fuses, dummy fuses and current limiters, and the rules for rating, replacing and carrying spare fuses. Then circuit breakers: how a thermal breaker trips, the white band that shows it has tripped, the vital difference between trip-free and non-trip-free breakers, and reverse current breakers. The second part is about the capacitor: what it is, what decides its capacitance, how it charges and discharges with the time constant, why it blocks direct current but appears to pass alternating current, and how to combine capacitors in series and parallel.
Part 1 · Protection
What can go wrong in a circuit + − fault path Short circuit + − Overload + − break Open circuit + − 35 V? Overvoltage Short circuit A low-resistance path bypasses the load: current soars . Heat (I² R) can melt cables and start a fire.
Overload Too much load on one circuit: current above the rating of the cable or equipment.
Open circuit A broken wire or connection: no current at all. The load stops, but nothing overheats.
Overvoltage A failed regulator raises the voltage: equipment can be damaged. Needs separate protection.
Chapter 3 · Circuit Protection and Capacitors
3
e-books by eatpl.in · © 2026 · Do not copy or distribute
Abnormal conditions in a circuit can cause either overcurrent or overvoltage, and if they are allowed to persist they will damage or destroy equipment, cut off essential power supplies, and in extreme cases cost lives. The most violent is the short circuit, where a low-resistance path bypasses the load, perhaps a chafed wire touching the airframe. The resistance collapses, the current soars, and because heating goes with current squared, cables can melt and a fire can start within seconds. An overload is milder: too many loads, or a failing motor, draw more current than the cable or equipment is rated for. An open circuit, a broken wire, stops the current altogether; the load fails, but nothing overheats, so a fuse does not blow. Overvoltage, perhaps from a failed voltage regulator, needs its own protection, covered later in the course. Fuses and circuit breakers are there to deal with overcurrent.
Part 1 · Protection
Fuse or breaker: when does each one act? 0 ½ max max time after the fault → fault current fuse opens here before full fault current circuit breaker opens after full fault current prospective fault current Breaker and the equipment must withstand the full fault current briefly But a breaker can be reset many times and used as a switch Illustrative shape, not to scale
Chapter 3 · Circuit Protection and Capacitors
4
e-books by eatpl.in · © 2026 · Do not copy or distribute
The fundamental difference between fuses and circuit breakers is when they operate, compared with the time the fault current takes to reach its maximum. When a short circuit happens, the current does not jump to its maximum instantly; it rises towards it, shown by the dashed prospective curve. A fuse normally melts and opens the circuit while the current is still rising, before the full fault current is reached. A circuit breaker is slower: it opens after the full fault current has been reached. That means that where breakers are used, both the breaker and the component it protects must be able to withstand the full fault current for a short time. In return, the breaker has a big advantage that the fuse has not: it can open and close the circuit, it can do so many times before it needs replacing, and it can also be used as an isolation switch.
Part 1 · Fuses
How a fuse works A fuse is a deliberately weak link : a wire or strip with a low melting point Fitted in series with the load, so it carries the full circuit current Current above its rating heats the element (I² R) until it melts and opens the circuit The time to blow varies inversely with the current : a big overload blows it fast Fuses are rated in amps , and work in both AC and DC circuits normal current: element intact element melted: circuit open element: low melting point wire or strip Fitted in series · rated in amps The bigger the overload, the faster it blows
Chapter 3 · Circuit Protection and Capacitors
5
e-books by eatpl.in · © 2026 · Do not copy or distribute
A fuse is a deliberately weak link in the circuit. Its element is a wire or strip made of a metal with a low melting point, and it is fitted in series with the load, so it carries the whole of the circuit current from the supply. Normal current warms it a little, but nothing more. When an overload pushes the current above the fuse’s rating, the heating, which goes with current squared, raises the element’s temperature until it melts in the middle. The gap breaks the circuit, the current stops, and the load goes cold. We say the fuse has blown. The time it takes varies inversely with the current: a small overload may take many seconds, a dead short only milliseconds. Fuses are rated in amps, the current they will carry continuously without overheating or deteriorating, and they work in both AC and DC circuits.
Part 1 · Fuses
The cartridge fuse Three basic fuse types: cartridge , high rupture capacity (HRC) and current limiter Cartridge fuse: a tubular glass or ceramic body , two brass end caps and an element Element: tinned copper wire , silver wire , or a strip of pure zinc (electro-tinned) The zinc strip, cut to a set width, is used in heavy-duty circuits Ratings range from about 0.5 A to 500 A ; the highest are HRC fuses or current limiters brass end cap glass or ceramic tube element Tinned copper wire light-duty circuits Silver wire accurate, light-duty Pure zinc strip, electro-tinned heavy-duty, cut to a set width Ratings from about 0.5 A to 500 A
Chapter 3 · Circuit Protection and Capacitors
6
e-books by eatpl.in · © 2026 · Do not copy or distribute
There are three basic types of fuse in use on aircraft: the cartridge fuse, the high rupture capacity, or HRC, fuse, and the current limiter. The cartridge fuse is the most common. It has a tubular body of glass or ceramic, two brass end caps that clip into the fuse holder, and the fusible element running between them. The element can be one of three things: tinned copper wire, silver wire, or a strip of pure zinc that has been electro-tinned. The zinc strip type is used in heavy-duty circuits, and the strip is cut to a specific width to set the current at which it will blow. Aircraft fuse ratings range from about half an amp up to around five hundred amps, but the higher ratings are limited to the HRC and current limiter types, which are built to handle the energy of a big fault safely.
Part 1 · Fuses
Time–current characteristics Every fuse has a time–current characteristic : the bigger the overload, the shorter the time to blow A small overload may be carried for seconds ; a short circuit clears in milliseconds This lets a fuse ride through brief, harmless surges , such as a motor starting A current limiter has a much slower curve: it carries a considerable overload before rupturing 1× 2× 5× 10× 20× 0.1 s 1 s 10 s 100 s 1000 s current ÷ rated current time to blow fuse current limiter Time to blow falls as the current rises (illustrative)
Chapter 3 · Circuit Protection and Capacitors
7
e-books by eatpl.in · © 2026 · Do not copy or distribute
Every fuse has a time–current characteristic, which shows how long it takes to blow at each level of overload. Both scales on this graph are logarithmic. Look at the blue fuse curve. At just over its rated current it might take minutes; at twice its rating, about ten seconds; at ten times its rating, a fraction of a second. So the time to blow falls steeply as the current rises. That shape is useful. It means a fuse can ride through a brief, harmless surge, such as the inrush when a motor starts, without blowing, yet still clear a real short circuit almost instantly. Now look at the current limiter curve, much further to the right and higher up. Its element has a high melting point, so it can carry a considerable overload for a long time before it ruptures. We will see in a moment where that is useful.
Part 1 · Fuses
Choosing the fuse rating The rating is the current a fuse carries continuously without unduly heating or deteriorating It must be not less than the normal circuit current… …but it must blow below the safety limit of the cable and equipment So the fuse protects both the cable and the load ; only the specified fuse may be fitted Example: 72 W at 24 V draws 3 A, so a 5 A fuse current → normal load fuse rating here cable / equipment safety limit not less than normal current · blows below the safe limit Worked example Circuit: 72 W at 24 V Normal current I = P ÷ V = 72 ÷ 24 = 3 A Choose the next size up: a 5 A fuse (24 A would not protect the cable)
Chapter 3 · Circuit Protection and Capacitors
8
e-books by eatpl.in · © 2026 · Do not copy or distribute
Choosing the right fuse is a balancing act. The rating is the current the fuse will carry continuously, or intermittently, without unduly heating up or deteriorating. On one side, the rating must not be less than the normal current flowing in the circuit, or the fuse would blow in normal use. On the other side, the fuse must blow at a current below the safety limit of the cable or equipment it protects. So a correctly chosen fuse protects both the circuit cable and the load, and for that reason only the specified fuse should ever be fitted in a particular circuit. Here is a typical exam calculation. A circuit uses seventy-two watts at twenty-four volts. The normal current is seventy-two divided by twenty-four, which is three amps. From the choices offered, you pick the next size up, a five amp fuse. A twenty-four amp fuse would let the cable overheat long before it blew.
Part 1 · Fuses
Replacing fuses, and spares Replace once only A blown fuse may be replaced once with one of the correct rating . If it blows again there is a defect : do not change it again until the circuit has been investigated.
Never uprate Never fit a higher rating or bridge a fuse holder: the cable would become the weak link and could burn.
Spare fuses Carrying spares is mandatory : at least 10% of the number of each rating installed, with a minimum of 3 of each.
Example: 12 installed 10% = 1.2, below the minimum, so carry 3 .
Example: 45 installed 10% = 4.5, so carry at least 5 .
Example: 80 installed 10% = 8, so carry 8 .
Chapter 3 · Circuit Protection and Capacitors
9
e-books by eatpl.in · © 2026 · Do not copy or distribute
There are firm rules about replacing fuses. A blown fuse may be replaced once only, with another of the correct rating. If the new one blows again when the circuit is switched on, there is a defect in the system, and the fuse must not be changed again until the circuit has been investigated. Never fit a fuse of a higher rating, and never bridge a fuse holder, because then the cable becomes the weakest link and could burn. Because fuses are consumed, carrying spares is mandatory. The quantity must be at least ten per cent of the number of each rating installed, with a minimum of three of each. So with twelve fuses of one rating installed, ten per cent is one point two, below the minimum, so you carry three. With forty-five installed, ten per cent is four point five, so you need at least five. With eighty installed, you carry eight.
Part 1 · Fuses
High rupture capacity (HRC) fuses An improvement on the cartridge fuse, used mainly for high-current circuits Robust ceramic body with one or more element holes, filled with powdered marble or clean quartz sand End caps of plated brass or copper Advantages: more accurate , operates without flame , no deterioration with age …more robust , operates rapidly , not affected by ambient temperature ceramic body quartz sand / powdered marble elements with notched (reduced) sections ✓ more accurate ✓ operates without flame ✓ does not deteriorate with age ✓ more robust ✓ operates rapidly ✓ not affected by ambient temperature Used mainly for high-current circuits
Chapter 3 · Circuit Protection and Capacitors
10
e-books by eatpl.in · © 2026 · Do not copy or distribute
The high rupture capacity fuse, or HRC fuse, is an improvement on the cartridge fuse, used mainly for high current circuits, where the energy released when a fuse blows can be very large. Its body is a robust ceramic, with one or more holes running through it for the elements. Those holes are packed with powdered marble or clean quartz sand, and the end caps are made of plated brass or copper. When the element melts, the sand absorbs the heat of the arc and quenches it, so the fuse clears without flame or blast. Learn its six advantages over the glass cartridge type. It is more accurate. It operates without flame. It does not deteriorate with age. It is more robust. It operates rapidly. And it is not affected by the ambient temperature around it.
Part 1 · Fuses
Dummy fuses and safety flags Circuits not in use have dummy fuses fitted When a fuse is removed to make a circuit safe for work , a dummy fuse or fuse holder replaces it Dummy fuse: red plastic , standard size, square corrugated centre, with a red streamer For circuit breakers , a warning flag or plate is clipped to the tripped (pulled) breaker dummy fuse red plastic, corrugated centre, red streamer DO NOT CLOSE tripped / pulled breaker with warning flag or collar Both show that a service has been made safe for work
Chapter 3 · Circuit Protection and Capacitors
11
e-books by eatpl.in · © 2026 · Do not copy or distribute
Sometimes a circuit must be made safe, so that work can be done on it, or it is simply not in use. If a fuse is removed to isolate a circuit, a dummy fuse, or a dummy fuse holder, is fitted in its place. A dummy fuse is made to standard fuse dimensions, but from red plastic, with a square centre section with corrugated sides so that it can be identified by touch, and a red streamer attached so it can be seen at a glance. Nobody can then put a real fuse back by mistake without noticing. Circuits protected by circuit breakers are made safe in a similar way: the breaker is pulled, and a warning flag or plate, often a coloured collar, is clipped over the tripped breaker to show that the service has been made safe for servicing and must not be reset.
Part 1 · Fuses
Current limiters Designed to limit the current to a predetermined value Thermal devices like fuses, but with a high melting point Carry a considerable overload for some time before rupturing So they protect heavy-duty power distribution circuits; a prime location is a TRU output Typical form: a tinned copper strip with a waisted centre, in a ceramic housing with an inspection window ceramic housing inspection window (glass or mica) bolt lug waisted centre = fusing area TRU DC bus limiter High melting point: carries a big overload for some time For heavy-duty power distribution circuits
Chapter 3 · Circuit Protection and Capacitors
12
e-books by eatpl.in · © 2026 · Do not copy or distribute
Current limiters, as the name suggests, are designed to limit the current to some predetermined value. Like fuses, they are thermal devices, but unlike ordinary fuses their element has a high melting point. That gives them a time–current characteristic that lets them carry a considerable overload current for some time before they rupture. For that reason they are used only to protect heavy-duty power distribution circuits, where large, short overloads are normal and you would not want a feeder to blow every time a big motor starts. A prime location is the output of a transformer rectifier unit, or TRU, feeding a DC bus bar. A typical current limiter is a single strip of tinned copper, drilled at each end for bolted connections, with its centre narrowed, or waisted, to form the fusing area. The centre is enclosed in a ceramic housing with an inspection window of glass or mica, so you can see whether it has ruptured.
Part 1 · Circuit breakers
Circuit breakers A circuit breaker combines the functions of a fuse and a switch Usually a thermal trip (bimetal) plus a manually or electrically operated switch; some add magnetic or reverse current trips Push-pull button types: about 5 to 45 A ; a white band shows when tripped Heavy-duty types may have a separate manual trip button Fitted in series with the load; used in AC and DC circuits 10 set 10 white band tripped 50 heavy duty manual trip Push-pull type: about 5 to 45 A Reverse current breakers: up to about 600 A Combine a fuse and a switch: pull to isolate Thermal trip; some also magnetic or reverse current
Chapter 3 · Circuit Protection and Capacitors
13
e-books by eatpl.in · © 2026 · Do not copy or distribute
A circuit breaker combines the functions of a fuse and a switch. It protects equipment from overload and fault conditions, and it can also be used to switch a circuit on and off, or to isolate it. Most breakers have an automatic thermal tripping device, a bimetal element heated by the load current, together with a manually or electrically operated switch. Some electrically operated breakers also have electromagnetic and reverse current trips. Watch the scene: an overload makes the current rise, the bimetal heats up and bends, and the breaker trips. The button pops out, and a white band appears on its stem. On a panel of dozens of breakers, that white band is how you spot the one that has tripped. The small push-pull breakers range from about five to forty-five amps, and heavier ones may have a separate manual trip button. Like fuses, breakers are fitted in series and work on AC and DC.
Part 1 · Circuit breakers
Inside a thermal breaker Set: current flows, latch holds 10 latch bimetal (carries the load current) contacts closed spring Overload: bimetal bends, latch releases, contacts snap open 10 latch hot bimetal (carries the load current) contacts open spring The bimetal is heated by the load current itself. A magnetic trip, where fitted, acts much faster on a heavy short circuit.
Chapter 3 · Circuit Protection and Capacitors
14
e-books by eatpl.in · © 2026 · Do not copy or distribute
Here is what happens inside a thermal circuit breaker. On the left, the breaker is set: the button is pushed in, a latch holds the mechanism, and the main contacts are closed, so the load current flows through them and through a bimetal element. This is the same differential expansion we met in the bimetallic switch. On the right, an overload has persisted. The extra current heats the bimetal, which bends, presses on the latch and releases it. A spring then snaps the contacts open, very quickly, so the arc is short, and drives the button outwards so that the white band shows. Because it works by heating, a thermal breaker takes a little time to trip on a modest overload, and it needs to cool before it can be reset. Where a magnetic trip is also fitted, a heavy short circuit pulls the latch magnetically and trips the breaker almost instantly.
Part 1 · Circuit breakers
Trip-free and non-trip-free breakers Non-trip-free fault present · button held IN button contacts held closed fault current flows Circuit IS made while held: clearly dangerous Both reset normally once the fault is cleared Trip-free fault present · button held IN button linkage released contacts open inside no current Circuit CANNOT be made while the fault persists Both reset normally once the fault is cleared
Chapter 3 · Circuit Protection and Capacitors
15
e-books by eatpl.in · © 2026 · Do not copy or distribute
Circuit breakers on the flight deck are either trip-free or non-trip-free, and the exam always asks about the difference. Imagine a fault that is still present, and someone pushes the reset button in and holds it there. In a non-trip-free breaker, the button is linked directly to the contacts, so holding it in holds the contacts closed and the circuit is made. Fault current keeps flowing, which is clearly dangerous. In a trip-free breaker, the mechanism trips free of the button: whatever you do with the button, the contacts open inside, so the circuit cannot be made while the fault persists. In both types, pressing the reset button will reset the breaker normally once the fault has been cleared. So the key phrase is: a trip-free breaker cannot be reset by holding the button in while the fault persists; a non-trip-free breaker can be held in, and the circuit will be made.
Part 1 · Circuit breakers
Reverse current circuit breakers Protect power supply systems against fault currents flowing the wrong way Act on reverse currents larger than those at which normal cut-outs operate Example: a failed generator being driven by the battery and the bus Remain locked out to isolate the circuit completely until the fault has been cleared Large ratings: up to about 600 A G generator RCCB bus bar + − battery normal reverse fault current Trips on reverse current larger than a cut-out would handle Then stays LOCKED OUT until the fault has been cleared Protects power supply systems (ratings to about 600 A)
Chapter 3 · Circuit Protection and Capacitors
16
e-books by eatpl.in · © 2026 · Do not copy or distribute
Reverse current circuit breakers protect power supply systems and their circuits against fault currents that flow against the normal direction, and that are larger than those at which the normal reverse current cut-outs operate. Picture a DC generator on the bus bar alongside the battery. Normally current flows from the generator to the bus. If the generator fails, the battery and the other sources on the bus can drive a heavy current backwards into it. A cut-out, which you will meet in the DC power chapter, handles small reverse currents. A large reverse fault current trips the reverse current breaker. Once tripped, it is designed to stay in a locked-out condition, so that the circuit is completely isolated until the fault has been found and cleared. These breakers handle big currents, with ratings up to about six hundred amps.
Part 1 · Summary of devices
Protection devices compared Device Works by Acts After operating Typical use Cartridge fuse Low-melting-point element Before full fault currentReplace (once only, correct rating) Light and medium circuits HRC fuse Element in quartz sand Rapidly, without flame Replace High-current circuits Current limiter High -melting-point stripOnly after a large, sustained overload Replace Power feeders, TRU outputs Thermal circuit breaker Bimetal releases a latch After full fault currentReset (many times)Most aircraft circuits; isolation Trip-free breaker As above, trips free of the button Cannot be held in on a fault Reset once fault cleared Flight-deck breakers Reverse current breaker Senses reverse current On large reverse fault current Locked out until fault clearedGenerator and power supply lines
Chapter 3 · Circuit Protection and Capacitors
17
e-books by eatpl.in · © 2026 · Do not copy or distribute
This table brings the protection devices together. The cartridge fuse has a low-melting-point element, acts before the full fault current is reached, and after blowing it is replaced, once only, with the correct rating. The HRC fuse has its element in quartz sand, acts rapidly without flame, and is used on high-current circuits. The current limiter has a high melting point and only ruptures after a large, sustained overload, so it is used on power feeders such as TRU outputs. The thermal circuit breaker uses a bimetal to release a latch, acts after the full fault current, and can be reset many times, so it doubles as an isolation switch. The trip-free breaker cannot be held in on a fault. And the reverse current breaker senses reverse current in power supply lines and locks out until the fault is cleared. All of them are connected in series with what they protect.
Part 2 · Capacitors
The capacitor Two metal plates separated by an insulator called the dielectric It stores electrical charge by creating an electric field between the plates It blocks DC once charged It appears to pass AC Symbols: non-polarised (either way round) and polarised : + terminal to the + supply dielectric (insulator) plate plate non-polarised + polarised (electrolytic) variable Stores charge · appears to pass AC · blocks DC
Chapter 3 · Circuit Protection and Capacitors
18
e-books by eatpl.in · © 2026 · Do not copy or distribute
Now part two, the capacitor. In its simplest form, a capacitor is two metal plates separated by an insulator called the dielectric, with a wire connected to each plate. It does three basic things. It stores electrical charge, by creating an electric field between the plates. It blocks direct current. And it appears to pass alternating current. Watch the scene. When the switch is closed, the battery pushes electrons onto plate Y, and electrons leave plate X and are drawn towards the battery, so current flows in the wires, even though nothing at all crosses the dielectric. As the plates charge, the current dies away until it stops completely. The diagram shows the circuit symbols. A non-polarised capacitor can be connected either way round, but a polarised type, such as an electrolytic capacitor, is marked with a plus sign, and its positive terminal must go to the positive supply.
Part 2 · Capacitors
Capacitance and what affects it Capacitance (C) measures the ability to store charge; unit the farad (F) Practical units: µF (10⁻⁶ F), nF (10⁻⁹ F), pF (10⁻¹² F) Larger plate area → larger capacitanceSmaller distance between the plates → larger capacitanceDielectric material : its dielectric constant k multiplies the capacitance (air 1, waxed paper about 3)C = k ε₀ A ÷ d C = Q ÷ V (farads) bigger area A C up smaller gap d C up better dielectric k C × k Air k = 1 · waxed paper k ≈ 3 → 3 × the capacitance Units: 1 µF = 10⁻⁶ F · 1 nF = 10⁻⁹ F · 1 pF = 10⁻¹² F Halve the gap → double C · double the area → double C
Chapter 3 · Circuit Protection and Capacitors
19
e-books by eatpl.in · © 2026 · Do not copy or distribute
Capacitance, symbol C, measures a capacitor’s ability to store electrical charge, and its unit is the farad. A farad is a very large unit, so in practice we use the microfarad, a millionth of a farad, the nanofarad, a thousand millionth, and the picofarad, a million millionth. Three things decide the capacitance. First, the area of the plates: bigger plates store more charge, so double the area and you double the capacitance. Second, the distance between the plates: bring them closer together and the capacitance increases; halve the gap and you double it. Third, the material of the dielectric. Each material has a dielectric constant, k. Air has a k of one, while waxed paper has a k of about three, so a capacitor with waxed paper between its plates has three times the capacitance of the same capacitor with air. Fuel is also a dielectric, which is exactly how capacitive fuel gauges work.
Part 2 · Capacitors
Working voltage The working voltage is the largest DC or peak AC voltage that may be applied It is often marked on the case Exceed it and the dielectric may break down : permanent damage On AC, use the peak : a 115 V AC supply peaks at about 163 V 0 90 180 270 360 -163 -115 0 115 163 angle (degrees) volts peak ≈ 163 V 115 V (AC value) Working voltage = largest DC or peak AC that may be applied across the capacitor Exceed it: the dielectric breaks down Polarised types: + terminal to the + supply
Chapter 3 · Circuit Protection and Capacitors
20
e-books by eatpl.in · © 2026 · Do not copy or distribute
Every capacitor has a working voltage, the largest DC voltage, or peak AC voltage, that can safely be applied across it. It is often marked on the case. If it is exceeded, the dielectric may break down: a spark punches through the insulator and the capacitor is permanently damaged, often short-circuited. Pay attention to the word peak. An alternating supply is usually described by its effective value, but the voltage actually swings higher than that at the top of each cycle. A one hundred and fifteen volt AC supply, which you will meet in the AC chapters, peaks at about one hundred and sixty-three volts, as the graph shows. So a capacitor on that supply needs a working voltage above one hundred and sixty-three volts, not just above one hundred and fifteen. You will learn where the factor between them comes from when we study AC.
Part 2 · Capacitors
A capacitor in a DC circuit Close the switch: electrons are pushed onto plate Y (negative) and leave plate X (positive) Electrons move in the wires , but no current flows through the dielectric As charge builds, a PD grows between the plates and the current falls When the plate PD equals the supply voltage , current stops : DC is blocked Disconnected, it holds its charge , and discharges only through an external circuit + − + − + − + − + − + − X Y + − e⁻ e⁻ no current through the dielectric Current flows until plate PD = supply voltage Then current stops: the capacitor blocks DC Disconnected, it holds its charge (energy in the electric field) until given a discharge path
Chapter 3 · Circuit Protection and Capacitors
21
e-books by eatpl.in · © 2026 · Do not copy or distribute
Let us look more closely at a capacitor in a DC circuit, in series with a battery and a switch. When the switch is closed, the battery pushes electrons onto plate Y, building up a negative charge there. That charge repels electrons from plate X across the dielectric, so they leave plate X and are drawn towards the positive terminal of the battery, leaving X positive. While this is happening, electrons are moving in the connecting wires, but no current passes through the dielectric itself. As the charge builds up, a potential difference grows between the plates, opposing the battery, so the current gets smaller and smaller. When the potential difference between the plates equals the supply voltage, the current stops. The capacitor is fully charged and is now blocking DC. If you then disconnect it, it holds its charge, storing energy in the electric field, and will only discharge when it is connected to an external circuit.
Part 2 · Capacitors
The time constant: how fast it charges 0 1 2 3 4 5 0 20% 40% 60% 80% 100% time (in time constants, τ = C × R) % of final value 63.2% 86.5% 95.0% 98.2% 99.3% current capacitor voltage Worked example R = 100 kΩ, C = 100 µF, 28 V supply τ = C × R = 100×10⁻⁶ × 100×10³ = 10 seconds after 10 s: 63.2% × 28 ≈ 17.7 V after 50 s (5τ): fully charged start current = 28 V ÷ 100 kΩ = 0.28 mA
Chapter 3 · Circuit Protection and Capacitors
22
e-books by eatpl.in · © 2026 · Do not copy or distribute
How fast does a capacitor charge? Through a resistor, the charging follows a curve set by the time constant, given the Greek letter tau, which equals the capacitance multiplied by the resistance, in seconds when you use farads and ohms. After one time constant, the capacitor voltage reaches sixty-three point two per cent of the supply. After two, eighty-six point five per cent; after three, ninety-five per cent; after four, ninety-eight per cent; and after five time constants it is over ninety-nine per cent, which we take as fully charged. The current, shown dashed, does the opposite: it starts at its highest value and falls away along the mirror-image curve. Now the worked example. One hundred kilohms and one hundred microfarads give a time constant of ten seconds. On twenty-eight volts, after ten seconds the capacitor is at about seventeen point seven volts, and after fifty seconds it is fully charged. The starting current is twenty-eight volts divided by one hundred kilohms, nought point two eight milliamps.
Part 2 · Capacitors
Discharging, and stored energy Connected across a resistor, a charged capacitor discharges along the same kind of curve After 1 τ the voltage has fallen to 36.8% ; after 5 τ it is practically zero A larger C or R gives a slower discharge Energy stored = ½ C V² Large capacitors can stay charged after power is removed: treat them as live 0 1 2 3 4 5 0 7 14 21 28 time (τ) volts 10.3 V (36.8%) under 1% after 5τ Discharges only through an external path Energy stored = ½ C V² 100 µF at 28 V: ½ × 100×10⁻⁶ × 28² ≈ 0.039 J Large capacitors can stay charged: a shock hazard
Chapter 3 · Circuit Protection and Capacitors
23
e-books by eatpl.in · © 2026 · Do not copy or distribute
When a charged capacitor is connected across a resistor, it discharges, and the voltage falls along the same kind of curve, set by the same time constant. After one time constant the voltage has fallen to thirty-six point eight per cent of its starting value; from twenty-eight volts, that is about ten point three volts. After five time constants it is below one per cent, practically zero. A bigger capacitance or a bigger resistance gives a longer time constant and a slower discharge. The energy stored in a capacitor is half the capacitance times the voltage squared; for one hundred microfarads at twenty-eight volts that is only about four hundredths of a joule, but large capacitors at high voltage store much more. Because a capacitor holds its charge until it is given a discharge path, a big one can still be charged long after the power has been switched off, so treat it as live until it has been safely discharged.
Part 2 · Capacitors
A capacitor in an AC circuit On AC the supply terminals change polarity every half cycle The capacitor charges, discharges, then charges the other way , continuously So current flows back and forth in the wires all the time: a lamp in series stays lit Still no current through the dielectric : the capacitor only appears to pass AC The current leads the voltage by 90° (more in the AC chapters) 0 180 360 540 720 -1 0 1 angle (degrees) voltage current Plates charge, discharge, then charge the other way: current never stops in the wires Still no current through the dielectric Current leads voltage by 90° So a capacitor appears to pass AC
Chapter 3 · Circuit Protection and Capacitors
24
e-books by eatpl.in · © 2026 · Do not copy or distribute
Now replace the battery with an alternating supply, and put a lamp in series with the capacitor. The supply terminals change from positive to negative and back again, at a rate set by the frequency. So the capacitor charges in one direction, discharges, and then charges in the opposite direction, over and over, for as long as the supply is connected. That means charge is always surging back and forth in the wires, and the lamp stays continuously lit. Yet there is still no current through the dielectric. The capacitor does not really pass alternating current; it only appears to. The graph shows another important feature: the current is greatest when the voltage is changing fastest, so the current wave peaks a quarter of a cycle, ninety degrees, before the voltage wave. We say the current leads the voltage. You will use that fact a great deal in the AC chapters.
Part 2 · Capacitors
Capacitors in parallel and in series Parallel: capacitances add C1 = 10 µF C2 = 22 µF A B C total = C1 + C2 = 10 + 22 = 32 µF Like adding plate area (this is how resistors add in series) Series: reciprocals add 10 µF 15 µF 1/C total = 1/10 + 1/15 = 5/30 → 6 µF or product ÷ sum: 150 ÷ 25 = 6 µF Less than the smallest: like a wider gap (this is how resistors combine in parallel) Capacitors combine the opposite way to resistors: parallel → add; series → reciprocals add.
Chapter 3 · Circuit Protection and Capacitors
25
e-books by eatpl.in · © 2026 · Do not copy or distribute
Capacitors combine the opposite way round to resistors, and the reason is easy to see. Connect capacitors in parallel and you are effectively increasing the area of the plates, so the capacitances simply add. Ten microfarads in parallel with twenty-two microfarads gives thirty-two microfarads. Connect them in series and you are effectively increasing the distance between the plates, so the total capacitance goes down, and you find it with the formula used for resistors in parallel: one over the total equals one over C one plus one over C two. For ten and fifteen microfarads in series, that is one tenth plus one fifteenth, five thirtieths, so the total is six microfarads, less than the smaller of the two. For just two capacitors, product over sum works as well: one hundred and fifty divided by twenty-five, six microfarads. Two equal capacitors in series give half the value of one.
Summary
What to take into the exam Timing Fuse opens before full fault current; breaker after , so both must withstand it briefly. Breakers can be reset.
Fuses Low melting point, in series, rated in amps. Rating ≥ normal current, below cable limit. Replace once only.
Spares and dummies Spares: 10% of each rating, minimum 3. Dummy fuse: red, corrugated, streamer.
HRC and limiters HRC: quartz sand, no flame, accurate, robust. Limiter: high melting point, heavy feeders, TRU output.
Breakers Fuse + switch. Bimetal trip, white band. Trip-free cannot be held in on a fault; non-trip-free can.
Reverse current Large reverse fault currents in supply lines; stays locked out until fault cleared.
Capacitance Area up, gap down, k up → C up. µF, nF, pF. Working voltage = max DC or peak AC.
Charging τ = C R: 63.2% after 1τ, full after 5τ. Blocks DC, appears to pass AC. Parallel add; series reciprocals.
Chapter 3 · Circuit Protection and Capacitors
26
e-books by eatpl.in · © 2026 · Do not copy or distribute
To finish, the exam points. A fuse opens before the full fault current is reached, a breaker after, so both the breaker and the equipment must withstand the full fault current briefly, but a breaker can be reset. A fuse has a low melting point, is fitted in series and rated in amps; its rating must be at least the normal current but below the cable’s limit, and it may be replaced once only. Spares are ten per cent of each rating with a minimum of three, and dummy fuses are red, corrugated and carry a streamer. HRC fuses use quartz sand and work without flame; current limiters have a high melting point and protect heavy feeders such as TRU outputs. Breakers combine a fuse and a switch, and a trip-free breaker cannot be held in on a fault. Reverse current breakers lock out. Capacitance rises with area and dielectric constant, and falls with the gap. The time constant is C times R, and capacitors add in parallel.